Application
The Conduspar Line of Multiplex Cables 1 kV is suitable for secondary circuits of power distribution and consumer connection in low voltage.
Construction
Phase conductor: Aluminum wires 1350, stringing class 2, compact, acc. to NM 280.
Insulation: thermosetting compound of XLPE (reticular polyethylene), weather resistant.
Identificación:
1 phase: black
2 phases: black and gray
3 phases: black, grey and red
Neutral conductor:
Aluminum CA: aluminum wires 1350, hardness H19, normal round stringing.
Alloy aluminum CAL: aluminum wires with alloy 6201, hardness T81, normal round stringing, acc. to 10298.
Neutral conductor insulation: if requested, in XLPE in light blue.
Maximum Operating Temperatures
In continuous regime: 90°C
In overload: 130°C
In short circuit: 250°C
Reference Standards
ABNT NBR 8182 – Self-sustained multiplex power cables with extruded insulation of PE or XLPE, for voltages up to 0,6/1 kV – Performance requirements.
ABNT NBR NM 280 – Conductors of insulated cables (IEC 60228, MOD).
ABNT NBR 10298 – Bare cables with alloy aluminum-magnesium-silicon, for overhead lines – Specification.
Conditioning
In rolls of 100 m or reels, for section up to 25 mm². For other constructions, in reels.
Nominal Dimensions
Cables with Neutral Aluminum – CA
Cables with Neutral in Aluminum Alloy 6201 – CAL