Application
The Conduspar Line of Toxfree Cable 1 kV is the safest solution for electrical installations, as it has a low smoke emission in case of fire. The standard NBR 5410 recommends the use of halogen-free and low smoke emission cables in installations in large concentrations of people with long and tumultuous escape routes (BD2, BD3 and BD4).
Construction
Conductor: bare electrolytic copper wires, soft hardness, stringing of class 5, acc. to NM 280.
Insulation: thermosetting compound of HEPR – ethylene propylene rubber.
Conductor colors: black, blue, white and red – in increasing order of conductor quantity.
Coverage and fillings: halogen-free polyolefin thermoplastic compound with fire retardant (SHF1).
Maximum Operating Temperatures
In continuous regime: 90°C
In overload: 130°C
In short circuit: 250°C
Reference Standards
ABNT NBR 13248 – Power cables and insulated conductors without coverage, halogen-free and with low smoke emission, for voltages up to 1 kV – Performance requirements.
ABNT NBR NM 280 – Conductors of insulated cables (IEC 60228, MOD).